Hi all.
Had a temp/humidity controller go toes up at work today and no spare. However in out panel we have a red Lion g15 HMI with a couple of modules plugged in. One being a analog unit and our temp and humidity sensors feed it using 4-20ma.
So did a quick program and drove a couple of outputs to control steam and heat relays.
however the input dances all over the place and I was wondering if anyone has a suggestion on how to dampen it a bit? I thought about using an array of tags and simply averaging say 10 tags but maybe there is already something there I dont know about.
Its a quick and dirty fix for now and a longer term solution will need to be sort but lets see if tonights production gets through