Does anyone know how to Setup up Port 2 of AD CPU 260 programmatically?

Join Date
Aug 2003
Posts
71
Does anyone know how to Setup up Port 2 of AD CPU 260 programmatically?

I need to set up Port 2 in my ladder as follow:


PROTOCOL: Non-Sequence
DATA BITS: 7
BAUD RATE: 9600
STOP BITS: 1
PARITY: Even

I could no find this in the User Guide.

Thanks all

Andy
 
Go to AutomationDirect's web site
Tech Support
Tech Support Home
Technical and Application Notes
Find AND2-002
Open and follow link on right side for Non-Sequence
 