RSLogix5000, How to put Communication Path

tx4129

Member
Join Date
Aug 2007
Location
thaialnd
Posts
21
I configed DF1 of CompactLogix with DL3500 converter(DF1 to DH+), I don't know how to config Message at communication path box link to DF1 port.

Appreciated your help
 
The Message Path for a DF1 message consists of the Port Number and the Destination Address.

On most Logix controllers, the serial port is Port 2.

A message addressed from a Logix controller to a DF1 device at Node 7 would use the path "2, 7".

CompactLogix controllers that have two serial ports (1769-L30, -L31) number them as Channel 0 = Port 2, Channel 1 = Port 3.
 