S7 Softing OPC to WONDERWARE

GNBLogic

Member
Join Date
Nov 2008
Location
KC
Posts
24
Hello,

Having issues with communication between Wonderware OPC Link and Softing OPC Server. It shows a Good Connection. I'm able to bring it up all the Block info on the softing demo without any issues. But, When i use WWClient with the OPC Link it gives me a Syntax Error. Not sure why? I have addressed as such DB30.DBD280 for a Real Number.

What am I doing wrong?

Thanks in Advance.
 
The addressing in intouch should be e.g.

rDB30,REAL280 for Reals
iDB30,INT280 for Integers
dDB30,X280.0 for Bits

remember and seperate with comma not full stop !!

hope this helps.

LH
 