I have a project where I have 2 slc on one panelview. Now I would like to have a numeric input thats writes to a parameter in each slc. How do I give a numeric input enable two different tags
 
The only way to write to two tags with one action is to use a Macro.

In FactoryTalk View, there is no way to make an ordinary Numeric Entry write to two controllers.
 