Mitsubishi Q2ASH CPU Error 2401 File set error

LLIyPiK

Member
Join Date
Feb 2017
Location
Vinnytsia
Posts
7
Hi to all!
Has anyone encountered such an error? What could be?

Error code list[Error code 2401]

Applicable machine QnA series PLC

=====================================================================================

Error code(SD0) 2401
Error message FILE SET ERROR
Common information(SD5-12) File name
Individual information(SD13-20) Parameter No.
LED status(RUN) OFF
LED status(ERROR) Flashing
PLC operating state Stop
Diagnostics timing At power ON & reset

Error description & cause

File designated for the fault history file (PLC RAS parameter setting), etc., cannot be created.

Corrective action

Read out the error individual information to a peripheral device, and check/correct the drive name and file name corresponding to that information(parameter No.)
Check the memory card’s remaining memory area.
 
Sounds like you are trying to create a file in the memory and there is not enough spare memory to create it, perhaps you have done this by accident
 

Similar Topics

Hello! If someone can help me with the following problem. I can't change the phone number. Do I really need the interface (AL-232CAB - Programming...
Replies
0
Views
30
how to communicate FactoryTalk Optix and Mitsubishi Q Series. I want to know the details of that
Replies
0
Views
36
I'm at a new job as the sole control engineer and trying to piece together where my predecessor left off. One machine I'm trying to get online...
Replies
2
Views
99
I'm looking to get some spare keys for this PLC. Does anyone know a source or have a part number? My searches are turning up nothing at the moment.
Replies
1
Views
76
Back
Top Bottom