Have anyone encountered liquid water inside junction and motor boxes as a result of condensation, not leakage? Solutions? An idea is 1 drilled hole in bottom that will allow gravity water out, but stop wind and dust blowing in..
An idea is 1 drilled hole in bottom that will allow gravity water out, but stop wind and dust blowing in..
Have anyone encountered liquid water inside junction and motor boxes as a result of condensation, not leakage? Solutions? An idea is 1 drilled hole in bottom that will allow gravity water out, but stop wind and dust blowing in..
Put a T at the lowest point, then flex UP to the device/motor from the center of the T and put one of these in the bottom.
http://www.cooperindustries.com/con...d_drains/cd_series_ordinarylocationdrain.html