Crocodile Tears
Member
First of all, I'm an AB guy and this GE/Emerson stuff is awful.
Problem I'm running into is - I have some backup files for seven PLCs on a site that are saved as plain files - they were not backed up as .zip, which PME/PAC/Whatever we're calling it these days, will not restore in the traditional method (right click in the project navigator, select restore, select zip, magic happens)
The method to get around this is make a new empty project, then on the empty project you right click, define the controller type, and then right click on the new target and select import. Select the folder and there is a versapro file in there to restore with.
This works, but only to an extent. I get an accurate hardware config, the variables and their comments come in, but I get no logic. If you look at the feedback zone, you can see it saying that it is importing the blocks, and no errors are thrown, but the ladder portion of the project is empty, nothing to click, nothing to select, just barren.
This is PAC 9.8, latest and greatest in theory. I checked with the only other semi controls jockey on site and he ran into the same thing. Does anyone have any thoughts on this? Seen it before? I thought I might be able to import the individual logic blocks, but when selecting that option, the file type needs to be .xml, which I do not have in these file folders.
Problem I'm running into is - I have some backup files for seven PLCs on a site that are saved as plain files - they were not backed up as .zip, which PME/PAC/Whatever we're calling it these days, will not restore in the traditional method (right click in the project navigator, select restore, select zip, magic happens)
The method to get around this is make a new empty project, then on the empty project you right click, define the controller type, and then right click on the new target and select import. Select the folder and there is a versapro file in there to restore with.
This works, but only to an extent. I get an accurate hardware config, the variables and their comments come in, but I get no logic. If you look at the feedback zone, you can see it saying that it is importing the blocks, and no errors are thrown, but the ladder portion of the project is empty, nothing to click, nothing to select, just barren.
This is PAC 9.8, latest and greatest in theory. I checked with the only other semi controls jockey on site and he ran into the same thing. Does anyone have any thoughts on this? Seen it before? I thought I might be able to import the individual logic blocks, but when selecting that option, the file type needs to be .xml, which I do not have in these file folders.