WinCC Flexible RT 2008 connection problem

MartinW

Member
Join Date
Apr 2008
Location
UK
Posts
70
Hi,

I have a WinCC Flexible 2008 project. It is configured as a PC RT. If I use the Runtime on my laptop (development environment) it works fine; communicates to PLC, displays values etc as you would expect.

However, I have installed WinCC Flexible 2008 RT including the licences onto another PC and the project starts but there are just ## where all the values should be, and I don't see the pop-up window which says whether the connection was successful or not.

I can ping the PLC from the PC so actual connectivity shouldn't be an issue.

The PLCs are all on the schema 10.96.25.xxx whereas all the PCs (including my laptop) are on 10.96.17.yyy. If the problem was the different IP schema then why does my laptop work ok?

I have ethernet enabled as channel 2 and I can send the project from my laptop to the target PC with no problem, but for some reason the thing doesn't want to communicate with the PLC?

Is this a Netpro thing? I don't know much about Netpro! :-( In Netpro there is no line from the WinCC to the CPU.

CPU is a 317-2 dp/pn.

Thanks,

Martin
 
Pg/pc

Check PG/PC interface. Set it on TCP/IP.

Too see if there is a connection, place an alarm window and set System Alarms on. Then you can see what happens.

Hi,

I have a WinCC Flexible 2008 project. It is configured as a PC RT. If I use the Runtime on my laptop (development environment) it works fine; communicates to PLC, displays values etc as you would expect.

However, I have installed WinCC Flexible 2008 RT including the licences onto another PC and the project starts but there are just ## where all the values should be, and I don't see the pop-up window which says whether the connection was successful or not.

I can ping the PLC from the PC so actual connectivity shouldn't be an issue.

The PLCs are all on the schema 10.96.25.xxx whereas all the PCs (including my laptop) are on 10.96.17.yyy. If the problem was the different IP schema then why does my laptop work ok?

I have ethernet enabled as channel 2 and I can send the project from my laptop to the target PC with no problem, but for some reason the thing doesn't want to communicate with the PLC?

Is this a Netpro thing? I don't know much about Netpro! :-( In Netpro there is no line from the WinCC to the CPU.

CPU is a 317-2 dp/pn.

Thanks,

Martin
 
Last edited:
Hi,

Thanks for your quick reply. However on the target PC all that is installed in WinCC Flex runtime - so no PG/PC interface to use?

Thanks,

Martin
 
Pg/pc

When installing WinCC Flexible, PG/PC interface is installed as well. Go to configuration panel and set the interface right so that Flexible know wich protocol it must use.


Hi,

Thanks for your quick reply. However on the target PC all that is installed in WinCC Flex runtime - so no PG/PC interface to use?

Thanks,

Martin
 

Similar Topics

Hi, We have upgraded our laptop which includes Windows 11. It appears that WinCC flexible 2008 advanced does not support Windows 11. What...
Replies
11
Views
285
Hello everyone I Have an Issue with the usage of recipes in Wincc Flexible 2008, I create the recipe to change the values in a fast way The...
Replies
0
Views
114
Hello Friends I have installed WinCC Flexible 2008 SP5 Update 2. I have open the software, but the Transfer option does not appear. Is It...
Replies
2
Views
1,483
I have wincc flex 2008 project made with wincc flexible 2088 sp1 project hmi device is simatic pc panel 19" I want to change hmi device to run the...
Replies
17
Views
5,299
Dear experts, I am Muhammad we have an IPC With the windows XP Embedded CE 5.0 on project and running well. i have plan to install wincc flexible...
Replies
8
Views
3,859
Back
Top Bottom