hello dear friends.
we have bought "proline prowirl 200 vortex flowmeter" but i dont know
which connector is for power supply.
i have read the whole manual but there isn't anything about
power supply connection.
please help me.
thanks.
thanks for your replies.
the flowmeter has pulse output and i am going to connect this pulse to s7300 plc.
in this case to where(which connection) should i connect the 24v power supply
in order to display turn on?
thanks.
No. You still need to complete the current loop connections to power the meter. The pulse out is a separate connection. Power supply plus can be connected to #3 and #4 goes to plc.