CPU 314-2 PN/DP, was online via laptop over ethernet, then CPU placed in STOP, MMC was removed and placed into SD card slot of an ordinary laptop (came up as 4+ separate storage devices, windows threatening to format all of them), MMC immediately removed from SD card slot with no changes or formats made, and placed back into PLC, and then PLC was switched to RUN mode. Now cannot go online with the PLC via ethernet (but can still ping it). What has happened? Was the MMC corrupted by the laptop SD port? Upon switching back to RUN, was the program in the PLC overwritten with corrupt data? If I get a MMC with the program on it, can I replace the existing one and the PLC will be restored? If I receive the backup in an email can I have someone with a siemens PG with MMC slot reformat the MMC and dump the emailed program onto it?