Hello, all!
Doing panel VFD (PF525) wiring.
Question about the wires on the VFD T1-T2-T3 output bus. The plan is to connect the T1-T2-T3 outputs to the terminals to which then the field wiring will be attached.
The field wiring will be VFD rated cables.
Do the short wires from the T1-T2-T3 outputs to the terminals need to be VFD rated cables or can be THHN wires which can handle the load (in my case THHN 600V AWG10 for the 1HP 480VAC load).
Thank you.