Modbus 485 connection wiring

sultanahmed

Member
Join Date
Jul 2013
Location
home
Posts
63
Hi,

I am working on Accuload 111 want to read/write data through modbus 485 through modbus poll software.
In device modbus connection shows RX+ RX- Tx+ Tx- conection. i have 2 wire seneca 485 to usb convertor i connect it with rx+ Tx+ is this configuration ok?
Please advise?
 
Hi,

I am working on Accuload 111 want to read/write data through modbus 485 through modbus poll software.
In device modbus connection shows RX+ RX- Tx+ Tx- conection. i have 2 wire seneca 485 to usb convertor i connect it with rx+ Tx+ is this configuration ok?
Please advise?

Link RX+ to TX+ and RX- to TX- together on the 4 wire end and connect your 2 wire USB lead to the + and - you have just linked

4 Wire_________2 Wire

RX+/TX+______+
RX-/TX-_______-

edit, just to note that wiring like this will only give you half duplex communications, not full duplex
 
Last edited:

Similar Topics

Hallo . I have a project to connect the Battery flow meter from SIEMENS Type : MAG 8000 ( RS 485 Modbus ) connection with USB MINI PC ( Simatic...
Replies
0
Views
3,912
I'm trying to control a device via MODBUS RTU and the ModbusRtuMasterV2_PcCOM in Twincat 3. I've configured a device with the right com port and...
Replies
7
Views
246
Does anyone know of an AOI using the user ASCII protocol select on the L6x controllers that will talk Modbus RTU using RS-485? Thanks, Trevor...
Replies
1
Views
150
Hello, I need to access the bits from the fire system control panel through RS-485. So, I used Read Var block to read from the panel...
Replies
0
Views
211
I am trying to figure out some communication specifics for a Modbus RTU network that I will be integrating with and could use some help to make...
Replies
9
Views
2,115
Back
Top Bottom