Thanks everyone for your comments.
OG, my scaling was just something simple to determine if it works. I actually have 0-10 Vdc input and need to display the value as 0-10.0.
Included is the rest of the ladder diagram, showing rung 0000. I am working from home today (without the PLC), so the diagram will not run.
The XIC in rung 0001 is my input, at 18 (.018Vdc) when off, 4825 when on.
OG I assume the crossover list shows any other use of the input (this will be helpful for my real program, this is just my analog input test program).
The issue that I saw (reference first picture) that while I had 4.825 Vdc on the input at I:4.8, I only had 18 written to N:10.6
To determine what the problem was, I created the second SCP referencing the same input, and used N10:1-4 to scale it. I would think copying the scaling from the top SCP to the bottom would give me the same output, but it didn't.
My question is why don't the outputs match?