S5 timer help

JIMCON

Member
Join Date
Sep 2005
Location
SWEDEN
Posts
124
Hello. its me again the S5 to S7 guy..

Now im stucked again. This time I dont understand this timer value:

KT 300.2 and KT 020.1

Is it seconds or hmm ? just want to be on the safe side..
 
Timer Dialog Box

Timer signals overview

SP, SE, SR, SS, SF Start timer
TV The Time Value is entered as a time constant (KT). The KT value consist of a number (in front of the decimal point) and a multiplier, the Time Base (after the decimal point) .
The following Time Bases are available:
Time Bases Example Time
0 = 0.01 sec KT 500.0 5 seconds
1 = 0.1 sec KT 050.1 5 seconds
2 = 1 sec KT 005.2 5 seconds
R Reset
BI Current counter value (Binary)
DE Current counter value (BCD)
Q Output

Pulse Timer
Extended Pulse Timer
On-Delay Timer
Latching On-Delay Timer
Off-Delay Timer




See if this helps
 

Similar Topics

I don't have much experience in programming. I can do simple configuration. it is like this. i want to add something to the existing ladder...
Replies
39
Views
6,333
Hi all, This is actually a personal project, if that's ok. My uncle has some property that has a well, he wants to have the well automatically...
Replies
7
Views
2,520
Hi there, I am accustomed to working with Logix 500 but have a program modification I need to do on a CompactLogix.... I created a timer...no...
Replies
7
Views
2,509
I have a conveyor whose speed varies between 20 and 50Hz through a PLC (HMI). I need to program a code with a timer whose value will vary between...
Replies
26
Views
4,495
Needing a panel mount style timer that would interface with a large numerical display. Tankline with 20000 + gallon dip tanks. Operators lower...
Replies
2
Views
1,934
Back
Top Bottom