Wonderware Convertion

paulmarlasuti

Member
Join Date
Mar 2009
Location
Chicago
Posts
7
Hi. I try to convert Wonderware App. from 7.1 to 9.5. But I got a problem. It got stuck when it was converting graphic to the new version. It has "Read Error" popup saying that "Cannot find DLL: "docview". If anybody can help me. Thank you
 
Document Viewer is an add on for Intouch that you can install from the old productivity package. You need to install that to get the Doc Viewer to work. I haven't used it since 8.0 so not sure if will run in 9.5.
If you have access to the PC running the 7.1 app, you can try copying the following before converting:
Copy the Docview.dll and Docview.wdo files into the InTouch folder (C:\Program Files\Wonderware\InTouch) and copy the View32W.dll file into the ArchestrA folder (C:\Program Files\Common Files\ArchestrA).
 
wonderware docview error

Hi Dave,
Thanks a lot for your post buddy. It helped me sort out my issue which I was struggling for a long time.
-Arun
 
Font changed after resolution conversion

I converted the wonderware application to a higher resolution and then converted back to original resolution. The fonts on my application look smaller than before. How can I change the fonts back?
 
I converted the wonderware application to a higher resolution and then converted back to original resolution. The fonts on my application look smaller than before. How can I change the fonts back?

Manually, I'm afraid. Unless, of course, you have a backup of the older version, and nothing has been modified since the application was converted.
 

Similar Topics

Hi guys, I have experience with PLC to Excel etc...just starting on using intouch scada screens. I have an Excel sheet that uses mainly...
Replies
1
Views
146
Hello everyone, Recently, my Archestra IDE shut down while I was editing. After restarting the IDE, I noticed warning symbols under my opened...
Replies
1
Views
101
Good morning all. I'm working on a rehab where they had a standalone InTouch 2014 HMI that they called a SCADA, but it's really basic stuff. The...
Replies
4
Views
182
Hi, We are setting up an Aveva Plant SCADA node with the intention to connect it to a Wonderware Historian node. Everywhere I look online I see...
Replies
1
Views
176
Hola chicos. Tengo un problema con el driver de comucicacion dasabcip 5, y un plc controllogix v34, ya realice la comunicacion pero en ciertos...
Replies
2
Views
158
Back
Top Bottom