Help with creating a one shot in S5

inst_tech

Member
Join Date
Jan 2010
Location
Scotland
Posts
58
Hi folks,

Am wondering if anyone can help (am sure its probably been asked before!). I'm trying to create a one shot in S5 but struggling. Have tried using set/resets but get in a right mess! Its simple with S7, click Pulse and thats it!

Any help greatly appreciated.
 
Hi folks,

Am wondering if anyone can help (am sure its probably been asked before!). I'm trying to create a one shot in S5 but struggling. Have tried using set/resets but get in a right mess! Its simple with S7, click Pulse and thats it!

Any help greatly appreciated.

A I 0.0
AN F1.7
=F 1.6
***
A I 0.0
= F1.7
***
F 1.6 is High for one scan of the PLC Program
 