Factory restore - Melsec FX1N

I've done this before but it was many years ago. From memory I believe it was a case of setting an M register and then cycling the power. I'm digging through my files to see if I can find which one it was.
 
Little bit of Copy&Paste....


Number M8032
Name Latch memory all clear
Contents OFF: Not all clear ON: All clear

Details

Current device settings are reset at next END, i.e. contacts, coils and current data values for Y,M,S,T,C and D devices respectively.
Special devices which have default settings are refreshed with those defaults.

Applicable CPU ALL FX CPU
 
Yes clear memory is what i wanna do,
and now i know how to:

Medoc:
Transfer - Other - Keyword, and down threre, PLC clear

GXIECdev 7.04
Online - PLC Clear - All
 

Similar Topics

Hello everybody, I can't restore a specific application, I don't have this problem with other applications. that I check Restore runtime...
Replies
6
Views
2,049
Hi all, i'm trying to restore an application with Rockwell's "Distributed Application Manager". And send me this error message: The application...
Replies
1
Views
1,549
I'm trying to restore a .MER file to a .APA file to edit in Factory Talk View Studio Release #6.00.00, Patch/Pack #00, Build #16. I started by...
Replies
3
Views
2,881
Hi, guys. I get an old AB PanelView 1000 (2711-T10C15, SER: D) from somewhere. But there is a password to stop me accessing to configuration...
Replies
17
Views
6,745
Hi all, some one can help me with a restore on Rockwell Factory Talk Transaction Manager? FTTM V10.10, run at Win7 64, Solidcore installed and...
Replies
1
Views
3,005
Back