Lord Farquaad
Member
Hi all
Longtime lurker, first time poster. Been in the industry for many years, of which the last 12 years have been in the mining industry. Currently busy with a project on a diamond mine in Botswana.
Anyway, I have a stupid question. I have an L75 controller in a V19 project. As always, RA keeps on updating firmware on their devices. Now I want to add a 1734-AENT module to the I/O Configuration. In RSNetworks for Ethernet it is listed as a Rev4.003. RSLogix only gives me the option to insert a V3.x module. I don't want to flash the module down to V3.x, and I also do not want to run it with Keying disabled. How do I get RSLogix5000 to give me the option to select it at Rev4.003?
I have done it before, but have forgotten how? Old age is a @#%$.
Longtime lurker, first time poster. Been in the industry for many years, of which the last 12 years have been in the mining industry. Currently busy with a project on a diamond mine in Botswana.
Anyway, I have a stupid question. I have an L75 controller in a V19 project. As always, RA keeps on updating firmware on their devices. Now I want to add a 1734-AENT module to the I/O Configuration. In RSNetworks for Ethernet it is listed as a Rev4.003. RSLogix only gives me the option to insert a V3.x module. I don't want to flash the module down to V3.x, and I also do not want to run it with Keying disabled. How do I get RSLogix5000 to give me the option to select it at Rev4.003?