Hi all,
I've come across an issue when trying to integrating an MovifitFC drive onto a L62 processor using V13.
The system is one of the oldest we have in the factory other systems we have are running Logix V30 on the L72 using the Movifit without an issue.
In the past we have intergrated an MoviPro ADC unit onto the v13 processor without any issues.
As the V13 doesn't support EDS files I've used the Ethernet module to create my own connection to the drive but even using the structure specified by SEW cannot get the drive to communicate. It keeps giving me a comms timeout message.
Has anyone got any ideas on what the issue my be or successfully done this elsewhere?
I don't really fancy upgrading this PLC to a new revision to due other equipment installed on the line
Thanks in advance