Need help to communicate pac3200 via micro850
Dear friends,
I need help, please. I use a PLC "micro850" which will read the data of an energy analyzer "Sentron PAC3200" via a Modbus TCP / IP protocol. Then, this micro850 will connect via an Ethernet CIP network with a "Controllogix". My problem was that the "PAC3200" gives a real Non swapped and I cannot recover the real real values. In my program, I used the instructions "MSG_Modbus2" and "COP" to program the micro850 for reading the real value from the "pac3200"and "MSG" instruction to program the controllogix for reading the CIP value from Micro850. thank you for your help. |
![]() |
![]() |
#2 |
Member
![]() ![]() Join Date: Nov 2016
Location: Fields of corn
Posts: 2,279
|
I've had similar problems on Control Logix and instead did the following:
Created an array of SINT variables (8 bit). Copied the real value into the SINT array. Swapped the bytes around in the correct order and COPied it back to a real value. Is this not possible to do on the micro850? |
![]() |
![]() |
#3 |
Member
![]() ![]() Join Date: Jan 2023
Location: tunisia
Posts: 2
|
Thank you for your reply,
The value output from the instruction "MSG_MODBUS2" is Word (16 bits). The objective is to reverse the first register (output of MSG_MODBUS2) with the second register to obtain the real value (32 bits). |
![]() |
![]() |
#4 |
Member
![]() ![]() Join Date: Nov 2016
Location: Fields of corn
Posts: 2,279
|
Same concept apply to what I wrote.
|
![]() |
![]() |
Currently Active Users Viewing This Thread: 1 (0 members and 1 guests) | |
Thread Tools | |
Display Modes | |
|
|
![]() |
||||
Thread | Thread Starter | Forum | Replies | Last Post |
how communicate Micro850 with kinetix 5100 and other third devices | KarajoSoft | LIVE PLC Questions And Answers | 1 | January 23rd, 2021 03:48 PM |
Micro850 Ethernet IP Connection to a third party device. | Roy24 | LIVE PLC Questions And Answers | 3 | July 10th, 2018 08:57 AM |
Communication Micro850 to OMRON CJ2M via Ethernet/IP | sonia kiangala | LIVE PLC Questions And Answers | 0 | July 31st, 2014 03:40 AM |
micro850 communicate with CompactLogix L30ER | Sergioalejan | LIVE PLC Questions And Answers | 2 | November 7th, 2013 12:08 PM |
Using PV+ nonvolatile memory (Micro850) | lolproe | LIVE PLC Questions And Answers | 0 | October 21st, 2013 03:07 PM |