Yes, I actually use PID. Based on Signets panel we are running about 60gpm so that is not a problem
I will try raw
Now I am confused based on harryting formula I have:
F8:20*(1/60000)*S:35 + F8:38
F8:20 running running SCP flow, F8:38 grand total
I get two operands in sequence error
To answer sthompson:
We have signet 8900 which is connected to flow meter and I am reading off 8900 panel. Between PLC and 8900 I have a discrepancy of 2-3k gallons a day
I am sorry, there is nothing else I can check the accuracy
Huh... Seems ok when I plug it into RSLogix 500, be sure you use the right symbol for division in 500 it's not a slash but a "vertical bar", try paste this:Now I am confused based on harryting formula I have:
F8:20*(1/60000)*S:35 + F8:38
F8:20 running running SCP flow, F8:38 grand total
I get two operands in sequence error