59
hello friends....

I have a problem with a project I'm currently doing with my 550 panel view when I want to download tell me I need the verification of the program I get a message of prevention....

I welcome your comments about my problem
 
Can you give us the complete message, some are just warnings and other are errors.
If just a warning you can still download.

Or maybe a screen shot or post the program. Zip it first.
 
hello friends....

I have a problem with a project I'm currently doing with my 550 panel view when I want to download tell me I need the verification of the program I get a message of prevention....

I welcome your comments about my problem

You need to describe your problem better.
What error messages are you getting?

You can make Panelbuilder verify your program without having to go through the download process. Actually, it is best to verify it and fix errors before you try to download it to the PV terminal.
 
Panelview 550

Hi friend.....

Thanks for your help to me...

I attached my proyect of panelbuilder32....

When i verify the proyect the message show....

I hope your comments and possible solution about it...

Thanks for all
 
Tag "TEMPPV2" does not exits in the database. You must create the tag in the tag editor.

Tag "TEMPPV1" does not have an address assigned to it. Look in the tag editor and assign it an address.

TagErrors.jpg
 
hello friend Thanks i do the adjustments to my project and i can download to pv...

In this project I want went some motor is turned off or switch does not close or open, show a message that tells me what happened ...

But I don't know do it...

You can teach me how I can do ...

Thanks i hope your comments soon thanks my friend...
 
ok my friend thanks for your help.....

just tell me what information you need to know to help me with my project and teach me what I have to do about it ...

I hope your comment ...
 
Your PLC will have to have motor status running/off. It will also have to have "switch" status open/close. Does it?

The PLC will have to know when the motor should to be running, same with the switch it has to know what position the switch should be in.

Then you can alarm when they are not.
 
Hi good day ..... Thanks for your help....

My project is an oven ....

which has the following:

I want use a plc slc 5/03 and panel view 550 for this project.

a main drive motor with vfd,
3 air circulation blower with a safety switch open each
a blower no.4 optional on/off
an exhaust blower with open safety switch,
a high gas switch closed
a low gas switch open,
blower burner 1 and 2,
two modules eclipse to turn the burners 1 and 2,
actuator 1 and actuator 2 of 4-20ma,
a motor with a switch breaker closed,
a motor with vfd for ac system,
a ext-blower motor,
a brush motor,
a motor with vfd roller,
a motor with vfd small belt,
a motor with vfd of sperder.

I hope your comments soon my friend...

This is all parts that have my project, if you want i can send you my file from the plc program
 
Ok, is this a working system and you just want to add some alarms to it?

If so see my post #9.

I am not going to write code for you, but I and forum members will help or make suggestions after you have made an attempt to do it yourself.

So go ahead and post your code. zip it first.
 
Last edited:
See picture below for a typical fail to start alarm.

Note if the pump fails to start within 25 sec (your system will dictate how long to wait)the alarm bit will become true. Your HMI would use this bit to alarm or create a message.

fail to start.jpg
 

Similar Topics

Hello all, I have a Panelview 550 Cat 2711-K5A5 that has one Serial port ( RS-232). Which I can talk to via my cable via DF1. Which is weird...
Replies
13
Views
2,430
Good evening partners, ist my first question on forum, i hope receive any answer. I need make a cable DH485 for communicate an Panel View 550...
Replies
3
Views
2,924
Hello, I have a panel View 550 that went bad , a new one has been installed , when you power up the PV it looks as it did before except there are...
Replies
6
Views
1,770
Panel view CAT number 2711-K5A2 Getting fault "612 No active mode found on network" Not sure if connected correctly and channel configuration is...
Replies
8
Views
2,028
Hi All - I know that this has been covered off previously but I can't find the right solution. I have a: PanelView 550 2711-T5A2L1X 4.41 Connected...
Replies
5
Views
2,775
Back
Top Bottom