We are doing a retrofit of a machine where Lenze servodrives are replaced with Siemens. However the Lenze servomotors are retained.
One of the problems we are facing is that the thermal sensor of the Lenze servomotors is KTY83, while the Siemens servodrives only allow KTY84 or PTC.
I am looking for a lowcost solution to evaluate the motor temperature.
A digital contact that signals overtemperature would be ok.
I only found one module : ABB C512-C513.
But I would like to know if anyone has experience with a same situation : read a KTY83 sensor and evaluate for overtemperature (if it is not connectable to the drive directly).
 
We are doing a retrofit of a machine where Lenze servodrives are replaced with Siemens. However the Lenze servomotors are retained.
One of the problems we are facing is that the thermal sensor of the Lenze servomotors is KTY83, while the Siemens servodrives only allow KTY84 or PTC.
I am looking for a lowcost solution to evaluate the motor temperature.
A digital contact that signals overtemperature would be ok.
I only found one module : ABB C512-C513.
But I would like to know if anyone has experience with a same situation : read a KTY83 sensor and evaluate for overtemperature (if it is not connectable to the drive directly).

WAGO's 857-820 will convert a KTY to an analog value...then any good analog alarm module will give you the contact closure.
 
Choose the temperature limit and adapt that resistance value by putting a suited resistor in series (or parallell)?

Edit: Might be unwise because of wrong temp in motor model calculations.


Or connect to the PLC with a card a la this:
https://cache.industry.siemens.com/...4xrtd_tc_2_3_4_wire_hf_manual_en-US_en-US.pdf

Kalle

Why should putting a suited resistor in series or parallel give wrong temperature model in motor model calculations?
Isn't it just some kind of scaling of the value towards the right value?
I am more and more thinking in the direction of the extra resistor.
 
If you can use the resistance solely as a protecting switch limit in the drive, you should be OK.

But I assume - not knowing - that if the drive has got an kty connected, it will be using the temp in the motor model calc.

If you manipulate a resistor like that, the curves will not be like the cuves from a real kty. The curves wil cross in the point you select - and the temp will show wrong values except in that particular point.

But it could still be worth a try ...

Kalle
 
Has anybody specific experience on applying motor temperature measurement and motor thermal model on Siemens Sinamics S120?
I should like to know if temperature measurement and motor thermal model have influence on motor regulation (current controller, torque controller) besides off course the warning and alarm message for overtemperature?
 

Similar Topics

Hello, fellow PLC enthusiasts, I’m a newbie in PLC and am currently on a project that involves connecting an Omron CP1E (CP1W-CIF11) PLC to an...
Replies
2
Views
55
I had trouble for a week trying to get a Marathon Symax Motor autotuned to work with a Powerflex 753 drive. I solved the problem and thought I...
Replies
0
Views
64
Hope you are doing well. Currently, I am involed in a revamping project. It requires to stop a mixer at specific postion. For the detail, this...
Replies
9
Views
321
I'm looking for how others do it. I need to start a 1 phase motor. I have always used a regular 3 phase Motor Protected Circuit Breaker and looped...
Replies
9
Views
256
I've got this 3-phase 575V motor that we're controlling with a VFD (Variable Frequency Drive), which has been quite the learning curve in itself...
Replies
10
Views
359
Back
Top Bottom