FactoryTalk View SE Multi-state Indicator issue

Chibu

Member
Join Date
Feb 2023
Location
Ontario
Posts
49
Hi Guys,

I configured some FactoryTalk SE multistate indicators but they only reflect state changes only after screen closure and reopening; also, when I talk them on the Screen they change state/colour.

Any ideas will be appreciated please.
 
Sometimes screen refresh rate is set too slow, causing no updates unless opening screen. Reduce refresh <1s and try
 
Hi Guys,

I configured some FactoryTalk SE multistate indicators but they only reflect state changes only after screen closure and reopening; also, when I talk them on the Screen they change state/colour.

Any ideas will be appreciated please.
Touch***
 
Are these supposed to be multistate Indicators or multistate pushbuttons?

Multistate pushbuttons can have value change based on previous value or previous state. If the indicator tag does not change than the state value won't update properly. Change to a momentary pushbutton instead of multistate pushbutton and do logic in the plc instead of the screen if needed more than one pushed state.
 
Are these supposed to be multistate Indicators or multistate pushbuttons?

Multistate pushbuttons can have value change based on previous value or previous state. If the indicator tag does not change than the state value won't update properly. Change to a momentary pushbutton instead of multistate pushbutton and do logic in the plc instead of the screen if needed more than one pushed state.
They are Multi-state indicators, I'm wondering why they can't update in real time without reopening the screen; and colour change when touched.
 
Are these supposed to be multistate Indicators or multistate pushbuttons?

Multistate pushbuttons can have value change based on previous value or previous state. If the indicator tag does not change than the state value won't update properly. Change to a momentary pushbutton instead of multistate pushbutton and do logic in the plc instead of the screen if needed more than one pushed state.
Thank you jholm90,
I mistakenly used Multistate Pushbutton instead of Multistate Indicator.

I appreciate your input.
 

Similar Topics

Hello, I had a question about benchmarking the Rockwell FactoryTalk View SE software. I've installed in the neighborhood of 30 different...
Replies
2
Views
300
I am working on a new View ME project for a demonstration display using a PC Hosted version of ME Station. I would like to show a cylinder...
Replies
4
Views
3,182
Hello, I have a panelview plus that reads from 4 different PLC's. 2 of these used to be Micrologix PLC's and someone else went and updated them to...
Replies
3
Views
64
Hi. I need to create several alarm servers in an application, but first I need to know if there is any impact on communication, or if more...
Replies
0
Views
59
Hello all, I'm having trouble opening an application. After clicking open I'm prompted to login and after putting in username & password it...
Replies
0
Views
85
Back
Top Bottom