Siemens-300 and ASi. Need help..

Jim.M

Member
Join Date
Dec 2008
Location
Sweden
Posts
77
Hello,

Right now im sitting here reading manual after manual from siemens.. This far i have now understod how to setup the AS-i slaves in "hardware config". But i cant really understand how to setup My AS-i Safety Monitor in step7.

I downloaded a sample project from Siemens.. but there where loads of blocks.. and I got really disorientated :oops:

I need an expert in this..o_O

There must be an easier way to setup ASI nodes and ASI monitor ???o_O


// Jim
 
Last edited:
Hi

I've done a project with the safety monitor connected to an S7-315 CPU long time ago. After doing an Upload of the AS-I slaves it configured itself.

The safety monitor runs it's own program. So I didn't use any of the S7 blocks. The AS-I master is only configured in my hardware config, in S7 I didn't program anything. The safety monitor does it's work to create emergency stops. I took feedback with a digital input.

Using the S7 blocks it for communication with the AS-I monitor, but it's not necessary for me.


Hello,

Right now im sitting here reading manual after manual from siemens.. This far i have now understod how to setup the AS-i slaves in "hardware config". But i cant really understand how to setup My AS-i Safety Monitor in step7.

I downloaded a sample project from Siemens.. but there where loads of blocks.. and I got really disorientated :oops:

I need an expert in this..o_O

There must be an easier way to setup ASI nodes and ASI monitor ???o_O


// Jim
 

Similar Topics

how can i obtain diagnostic data out of p an f asi master can i use read rec as when using 343-2
Replies
0
Views
5,251
Hi, I'm setting up a modbus master on an S7-300. It seems to work in OB1 but not when I use it in OB35. Does anyone have any ideas why? Could...
Replies
10
Views
123
Hello all. I have an ESA HMI that is connected to a Simatic S7-300 (CPU312). I have uploaded the program from the PLC which is written with Step7...
Replies
6
Views
1,480
Hello. There is a problem with Siemens S7 300. We got a replacement PLC but it does not run the program from the MMC. The new PLC is dated 2011...
Replies
3
Views
725
Hi to all, Our company does not usually use Siemens PLCs, but have a press with one in it. We are trying to change the IP address in our Simatic...
Replies
2
Views
1,082
Back
Top Bottom