CPU317T-2DP firmware update

pasimanninen

Member
Join Date
Jan 2008
Location
Joensuu
Posts
22
is it only way to buy very expensive siemens usb prommer that i can execute firmware update to cpu317t-2dp PLC.

Working online on tecnology object is impossible because on PLC TO(technology object) firmware is 3.0.1 but my S7T config version is 3.1.1.

What can i do , can some wizard tell me cheaper or easier ways solve my little problem ????

Best regards

Pasi Petteri Manninen
Finland
 
Hello : step of upgrade fireware as below
1. you need 8 mb mmc card for upgrade fireware
2. insert 8mb mmc card to PG
3. copy fireware you want upgrade to mmc card from Step 7
(use PG ) then insert to plc
4. during power on switch to rest until sf ligh up
and stop light flash (fireware download )
5. stop light slow down flash (finish download )
6. Power off
7. insert new mmc card then Power On
 

Similar Topics

Dear sir, I am using SIMATIC 300, CPU 315-2DP , (6ES7 315-2AF03-0AB0) VIPA 603-1CC21 A1.0 RAM 32KB, Firmware=V4.0.8 The problem Im using MPI...
Replies
2
Views
164
Hi , Looking for some help. We have a 343-1 PN Lean Card & 315-2DP connected to an external system collecting data. After a recent shutdown...
Replies
0
Views
65
I'll preface this by saying this is the first time I've worked on a Siemens system and I'm fairly unfamiliar with them. I might mess up some of...
Replies
29
Views
740
Dear Experts, We have fourteen CPU 314C-2DP units that are interconnected with PROFIBUS and we have an IE/PB module to convert from PROFIBUS to...
Replies
3
Views
849
Hi We were having a few power cuts and the CPU would not work. I had to reset the memory and he CPU would read from the memory card and start...
Replies
13
Views
3,157
Back
Top Bottom