Goto configure mode

It's up there in the Objects menu, I just didn't have FTView Studio running at the moment to give you the exact clicks.

I sometimes during commissioning animate the visibility of the Goto Config button by using the controller keyswitch mode; when I'm in Remote Run it's OK to mess with the PanelView, but not in hard RUN mode. You can also use a controller tag or a logged-in user permission, or put it on a password-secured display.
 