some of the existing ethernet IO modules having problems after adding couple camera(Keyence IV3).Tried swapping the switch with a bigger one. Didnt help.
Tried to group the IO modules into a smaller switch and other connections into the bigger switch i mentioned earlier. but still not helping.
 
It is a Compactlogix 5323E-QB1. How do I find the capacity?

Page 159 mentions capacity. It seems to be 32 for the Compactlogix Packaged controllers.

https://literature.rockwellautomation.com/idc/groups/literature/documents/qs/iasimp-qs010_-en-p.pdf


You might also want to check the RPI setting for your new devices and slow it down. Depending on your network architecture, this might cause your communication to break down.

More info would be needed, like screenshots etc. to pin this issue.
 

Similar Topics

Hello all, I have a 1756-EN2TR dual-port Ethernet IP Module attached to my 1756-L73 PLC. I currently have hazard symbols over both the top and...
Replies
9
Views
186
Hi, We have been facing a issue with SCADAPack 474. Configuration is like below. RTU 474 + 6103 PS + 5606 IO Mix Module + 5414 DI Module Only...
Replies
0
Views
84
hello, I have a Maple Systems HMI5103L currently programed and running in conjunction with a AB 2080-LC50-24QWB. everything works fine data is...
Replies
2
Views
737
Have tried to get the tag details from the PLC through python pycomm module.But getting Tag doesn't exist error. Am using pycomm version = 0.11.0...
Replies
1
Views
527
Hi everyone. I worked with RedLion HMI several years, in the last year four CR3000 HMI (10 and 15") had have problems with the touchscreen. All...
Replies
5
Views
1,307
Back
Top Bottom